고객센터
Customer Center
Customer Center
→ VBE602,603,604/VBS602,603,604/VBH602,603,604/VBL602,603,604
Frame |
600AF | |||
Model |
Type |
Economic Type |
Standard Type |
Current Limiting Type |
2 poles |
VBE 602 |
VBS 602 |
VBL 602 | |
3 poles |
VBE 603 |
VBS 603 |
VBL 603 | |
4 poles |
VBE 604 |
VBS 604 |
VBL 604 | |
Rated Current(In) |
500, 600A | |||
Rated Insulation Voltage(Ui) |
AC |
690V |
690V |
690V |
Rated Breaking Current KSC8321(Sym) IEC60947-2(Icu) |
AC600V |
22kA |
35kA |
42kA |
AC500V/480V |
25kA |
45kA |
50kA | |
AC460V |
35kA |
50kA |
65kA | |
AC415V |
35kA |
50kA |
65kA | |
Ics=0.5xIcu |
AC380V |
35kA |
50kA |
65kA |
AC220V |
50kA |
100kA |
125kA | |
DC250V |
20kA |
40kA |
40kA | |
Endurance(times) |
Mechanical |
4,000 | ||
Electrical |
1,000 | |||
Over Current Tripping Device |
Thermal Magnetic(TM) | |||
Installing Method |
Standard |
Screw | ||
Weight(kg) |
2 poles |
11kg | ||
3 poles |
11.5kg | |||
4 poles |
18.2kg |