ATS:66-616CT

비츠로이엠 2017-12-21 조회수 2,624
ATS:66-616CT

 


Frame

66CT

610CT

616CT416CT

Rated Current(In)

A

600

800,1000

1200,1600

Rated Voltage(Ue)

V

AC600

AC600

AC600AC415V

Rated Insulation Voltage(Ui)

V

AC800

AC800

AC800│AC600V

Rated Impulse Voltage(Uimp)

kV

8

8

8│6

Pole

P

3,4

3,4

3,4

Throw

T

Double Throw

Double Throw

Double Throw

Connection Type

Front

Back

Performance

Short Time Current(1s)             lcw

kA

15

25

32

Short Circuit Peak Current          lcm

kA

15

25

32

With Specific Circuit Breaker

kA

50

50

65

Fuse Mounting

kA

200

200

200

Switch Capacity Note1)

Class

AC-33B

AC-33B

AC-33B

Endurance

Electrical

5,000

5,000

5,000

5,000

Mechanical

10,000

10,000

10,000

10,000

Transfer Sequence

Aoverlapping↔B, A↔B, A↔Neutral(off)↔B

Conduction for Uninterrupted Switchover

Phase difference : Within electrical angle 10°, Frequency difference : Within 0.2Hz,

Voltage : Voltage difference with the commercial one is within 5%,

Instantaneous Interconnection Time : Within 0.05 second

Operation Time

Closing

msec

150

150

150

Trip

msec

30

30

60

Conditions of Uninterruptible Transfer

3P

4P

3P

4P

3P

4P

Closing

AC/DC 110V

A

7

8

8

10

10/16

13/16

AC 220V

A

3.5

4

4

5

5/8

6.5/8

Trip Note2)

AC/DC 110V

A

4

4

4/4

AC 220V

A

2

2

2/4

Dimensions & Weights

Front Size(mm)

 

H

545

545

607

607

644

644

W

465

530

510

590

570

670

D

219.4

219.4

219.4

219.4

219.4

219.4

Back Size(mm)

H

478

478

478

478

478

478

W

465

530

510

590

570

670

D

254.4

254.4

299.4

299.4

299.4

299.4

Weight

Front

kg

53

61

66

76

72

84

Back

kg

-

-

-

-

72