본문 바로가기 주메뉴 바로가기

고객센터

Customer Center

QR

home > 고객센터 > QR

 

ATS:64CT

비츠로이엠 2017-12-21 조회수 2,843
ATS:64CT

 

 

Frame

64CT

Rated Current(In)

A

400

Rated Voltage(Ue)

V

AC600

Rated Insulation Voltage(Ui)

V

AC800

Rated Impulse Voltage(Uimp)

kV

8

Pole

P

2,3,4

Throw

T

Double Throw

Connection Type

Front

Back

-

Performance

Short Time Current(1s)             lcw

kA

12

Short Circuit Peak Current          lcm

kA

12

With Specific Circuit Breaker

kA

35

Fuse Mounting

kA

200

Switch Capacity Note1)

Class

AC-33B

Endurance

Electrical

Cycles

5,000

Mechanical

Cycles

10,000

Transfer Sequence

Aoverlapping↔B, A↔B, A↔Neutral(off)↔B

Conduction for Uninterrupted Switchover

Phase difference : Within electrical angle 10°, Frequency difference : Within 0.2Hz,

Voltage : Voltage difference with the commercial one is within 5%,

Instantaneous Interconnection Time : Within 0.05 second

Operation Time

Closing

msec

100

Trip

msec

30

Conditions of Uninterruptible Transfer

2P

3P

4P

Closing

AC/DC 110V

A

7

7

9

AC 220V

A

3.5

3.5

4.5

Trip Note2)

AC/DC 110V

A

4

AC 220V

A

2

Dimensions & Weights

Front Size(mm)

 

H

307

307

307

W

292.5

352.5

412.5

D

132

132

132

Back Size(mm)

H

-

-

-

W

-

-

-

D

-

-

-

Weight

Front

kg

14

17

21

Back

kg

-

-

-

Additional Product Information

Circuit diagram

A6-24

Drawing

A6-40~42

Precautions

A6-18


64CT.png

 

 