ATS:625WN-630WN
Frame |
625WN |
630WN | |||||
Rated Current(In) |
A |
2500 |
3000 | ||||
Rated Voltage(Ue) |
V |
AC600 |
AC600 | ||||
Rated Insulation Voltage(Ui) |
V |
AC800 |
AC800 | ||||
Rated Impulse Voltage(Uimp) |
kV |
8 |
8 | ||||
Pole |
P |
3,4 |
3,4 | ||||
Throw |
T |
Double Throw |
Double Throw | ||||
Connection Type |
Front |
- |
- | ||||
Back |
● |
● | |||||
Performance | |||||||
Short Time Current(1s) lcw |
kA |
50 |
50 | ||||
Short Circuit Peak Current lcm |
kA |
50 |
50 | ||||
With Specific Circuit Breaker |
kA |
85 |
85 | ||||
Fuse Mounting |
kA |
200 |
200 | ||||
Switch Capacity Note1) |
Class |
AC-33B |
AC-33B | ||||
Endurance |
Electrical |
Cycles |
3,000 |
3,000 | |||
Mechanical |
Cycles |
5,000 |
5,000 | ||||
Transfer Sequence |
A↔B, A↔Neutral(off)↔B | ||||||
Operation Time |
Closing |
msec |
≤180 |
≤180 | |||
Trip |
msec |
≤35 |
≤35 | ||||
Conditions of Uninterruptible Transfer |
3P |
4P | |||||
Closing |
AC/DC 110V |
A |
- |
- |
- |
- | |
AC 220V |
A |
12 |
15 |
12 |
15 | ||
Trip Note2) |
AC/DC 110V |
A |
- |
- | |||
AC 220V |
A |
2 |
2 | ||||
Dimensions & Weights | |||||||
Front Size(mm)
|
H |
- |
- |
- |
- | ||
W |
- |
- |
- |
- | |||
D |
- |
- |
- |
- | |||
Back Size(mm) |
H |
378.5 |
378.5 |
378.5 |
378.5 | ||
W |
602.5 |
735.5 |
602.5 |
735.5 | |||
D |
326 |
326 |
326 |
326 | |||
Weight |
Front |
kg |
- |
- |
- |
- | |
Back |
kg |
92.5 |
119 |
92.5 |
119 | ||
Additional Product Information | |||||||
Circuit diagram |
A6-19 |
A6-19 | |||||
Time chart |
A6-18 |
A6-18 | |||||
Drawing |
A6-32 |
A6-32 | |||||
Precautions |
A6-14 |
A6-14 |