ATS:610WN
Frame |
610WN | ||||
Rated Current(In) |
A |
1000 | |||
Rated Voltage(Ue) |
V |
AC600 | |||
Rated Insulation Voltage(Ui) |
V |
AC800 | |||
Rated Impulse Voltage(Uimp) |
kV |
8 | |||
Pole |
P |
3,4 | |||
Throw |
T |
Double Throw | |||
Connection Type |
Front |
● | |||
Back |
● | ||||
Performance | |||||
Short Time Current(1s) lcw |
kA |
22 | |||
Short Circuit Peak Current lcm |
kA |
22 | |||
With Specific Circuit Breaker |
kA |
50 | |||
Fuse Mounting |
kA |
200 | |||
Switch Capacity Note1) |
Class |
AC-33B | |||
Endurance |
Electrical |
Cycles |
5,000 | ||
Mechanical |
Cycles |
10,000 | |||
Transfer Sequence |
A↔B, A↔Neutral(off)↔B | ||||
Operation Time |
Closing |
msec |
≤100 | ||
Trip |
msec |
≤30 | |||
Conditions of Uninterruptible Transfer |
3P |
4P | |||
Closing |
AC/DC 110V |
A |
10 |
10 | |
AC 220V |
A |
5 |
5 | ||
Trip Note2) |
AC/DC 110V |
A |
4 | ||
AC 220V |
A |
2 | |||
Dimensions & Weights | |||||
Front Size(mm)
|
H |
298 |